| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Rail or terminals 11+, 12- | |
| Rated voltage | 20 ... 35 V DC | |
| Ripple | within the supply tolerance | |
| Rated current | < 20 mA | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 4+, 5- | |
| Input resistance | min. 10 MΩ | |
| Transmission range | 0 ... 9 V | |
| Offset voltage/current | < 2 mV / < 7 nA | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 7-, 8+ | |
| Voltage | 0 ... 9 V | |
| Output resistance | ≤ 20 Ω | |
| Transfer characteristics | ||
| Cut-off frequency | 1.2 kHz (-3 dB) | |
| Deviation | ||
| After calibration | ± 5 mV at 20 °C (68 °F) | |
| Influence of ambient temperature | ≤ 0.005 % of range per K | |
| Rise time | ≤ 0.4 ms | |
| Galvanic isolation | ||
| Output/power supply | Basic insulation according to DIN EN 50178, rated insulation voltage of AC 50 V | |
| Indicators/settings | ||
| Display elements | LED | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Insulation coordination | EN 50178 | |
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 100 g | |
| Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-type examination certificate | DMT 01 ATEX E 133 | |
| Marking |
I (M1) [Ex ia] I
|
|
| Voltage | 12 V | |
| Current | 2.8 mA | |
| Power | 8.4 mW | |
| Supply | ||
| Maximum safe voltage | 250 V (Attention! The rated voltage is lower.) | |
| Output | ||
| Maximum safe voltage | 250 V (Attention! The rated voltage is lower.) | |
| Galvanic isolation | ||
| Input/Output | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Input/power supply | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
| General information | ||
| Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. | |
| System | Classcode |
|---|---|
| ECLASS 11.0 | 27210120 |
| ECLASS 10.0.1 | 27210120 |
| ECLASS 9.0 | 27210120 |
| ECLASS 8.0 | 27210120 |
| ECLASS 5.1 | 27210120 |
| ETIM 8.0 | EC002653 |
| ETIM 7.0 | EC002653 |
| ETIM 6.0 | EC002653 |
| ETIM 5.0 | EC001485 |
| UNSPSC 12.1 | 32101514 |